    Hot work is usually defined as any open flame, spark or heat producing activity and is typically associated with cutting, welding, grinding and brazing operations as part of maintenance or construction works.

    Hot work can generate sparks, molten material and other ignition sources well away from the area of work. In addition, conducted heat can cause ignition of combustible materials both locally and remotely.

    Ideally hot work should not be carried out and alternative methods of work should be investigated. If there is no alternative, then every effort should be made to relocate the activity to a designated safe area well away from buildings and structures or to a properly designed and constructed workshop area.

    The decision to carry out hot work when the above criteria cannot be met should be a conscious one after all other alternatives have been exhausted. At this stage a formal Hot Work Permit and procedure should be used. This applies to everyone – staff or contractors alike.

    Hot work has been recognised as a significant fire risk for many years. Despite this, loss statistics show us that it continues to be a major cause of loss within industrial and commercial facilities, particularly during mintenance periods and construction projects.

    It is essential that all hot work activities are properly managed.

    © Getty Images/Antonio Hugo/xsw
    2025 construction trends: UK & Ireland - Download our industry reports
    Explore key trends that are reshaping the future of their respective construction markets

    Hot work procedure

    Hot work and timber frame construction

    Hot work on timber frame construction sites should be minimised. Where hot work cannot be avoided, in addition to the standard controls for hot work, the area in which the work has been undertaken must be continually monitored for at least one hour following completion of the hot works and be visited two hours after completion prior to closing the permit.

    Exposed wooden flooring and other items of combustible material which cannot be removed must be covered with sand or other non-combustible material.

    All hot work undertaken outside of a designated 'safe' hot work area or within 15m of buildings, structures or external storage should fall under a Hot Work Permit.

    This should be fully documented, adopted as a company standard and applicable to all employees, contractors and visitors. As a minimum the procedure should contain the following:

    • Definition of hot work
    • Scope of application of procedure
    • A dedicated permit for the control of hot work activities – Hot Work Permit
    • Training requirements for Hot Work Permit issuers, including refresher training timescales
    • A list of those trained and authorised to issue Hot Work Permits
    • Requirement for periodic audit of the Hot Work Control
    • Procedure including live and completed Hot Work Permits

    Hot Work Permits

    The use of a dedicated permit to control hot work activities forms an essential part of a hot work process, but it is not the only level of control needed. Many losses have occurred where permits have been issued but these have not been properly completed, or the precautions identified have not been properly implemented, or those issuing the permit do not recognise all the potential hazards.

    Authority to issue permits should be granted following successful completion of appropriate training and demonstration of competence.

    The key criteria for a Hot Work Permit are:

    • Permits should be issued for a specific task in a specific location.
    • Permits should be issued to a named individual and only for that individual to carry out the hot work.
    • Permits should not be issued for more than one day or shift (8 hours).

    Extensions to permits are acceptable provided all necessary precautions are re-checked and the extension is formally documented.

    A copy of the issued permit should be available at the place where the work is being carried out. This allows those carrying out the work to demonstrate that they have the appropriate permission. The issued permit also acts as a checklist to allow review of the conditions under which the permit was issued. Should any of these conditions change then work should be suspended. Resumption of work should only be undertaken when authorised by the original permit issuer.

    Fire watch

    A fire watch should be posted during the work. As a minimum this should be one person with a fire extinguisher or hose, but could require additional observers if the work is being done close to pits, trenches or cable trays, or near penetrations through walls or floor or ceilings, or on tall or combustible structures. The person doing the hot work should never be allowed to be their own fire watch. Note that the fire watch should be maintained during breaks in the work such as at refreshment breaks.

    Statistically the majority of major losses have occurred sometime after the hot work has been completed. Smouldering materials may go unnoticed and develop into fires when the area or building is unoccupied. A fire watch should always be undertaken during the work and following completion of the work. The period of the postwork fire watch should be based on the hazards present. The minimum post-work fire watch should be continuous for 30 minutes then periodic inspection of the work place and surrounding area (including floors below where the floor is penetrated) for at least another 30 minutes. Where there is a significant combustible loading within the building or combustible construction is present, the periodic inspections should be extended to 2 hours or more after the work is completed.

    To ensure an adequate fire watch can be achieved, hot work should not be allowed within 2 hours of the end of the normal shift when operations would normally cease and staff leave for the night.

    Checklist before hot work commences

    • At least 2 suitable portable fire extinguishers should be available for immediate use within the area of hot work operations and all persons involved and undertaking fire watch duties be trained in their use. Any sprinkler protection should remain fully operational. Any automatic fire detection systems should be isolated only in the area where hot works is undertaken and only for the period of the work.
    • Inspections should be made and combustible materials and flammable liquids should be removed from:
      • an area within 10 metres of the hot work
      • floors above and below, and areas on the other sides of walls, screens or partitions which may be in danger of ignition either directly or from conducted heat.
    • Floors of combustible material in the designated area should be covered with sheets of incombustible protective material or wetted and covered with sand if there are any:
      • combustible materials that cannot be removed
      • holes, gaps in walls, floors or ceilings where sparks could pass through they should be covered by incombustible material.
    • Where work is carried out on building panels, an assessment should be made on insulating or other materials behind or forming the core of the panels.
    • Allow adequate ventilation and ensure enclosed equipment such as tanks, vessels, etc, are emptied and tested to ensure that they are free of flammable or other dangerous materials.
    • Identify any gas pipes or other services adjacent to or below the area of hot work and isolate and protect them.
    • All persons carrying out the hot work and undertaking the fire watch should know how to raise the fire alarm and be aware of any emergency procedures.
    • Confirm all other contractors/operators on site are aware that hot work is being undertaken, and that there is no application of paints or flammable solvent based chemicals.

    References:

    • FPA RC7 – Recommendations for Hot Work
    • NFPA 241: Standard for Safeguarding Construction, Alteration, and Demolition Operations Current Edition: 2022
    • The Joint Code of Practice on the Protection from Fire of Construction Sites and Buildings Undergoing Renovation, 10th Edition (August 2022)
    Disclaimer: The guidance in this document refers to industry best practice loss control advice. Adoption of the advice contained within this document does not imply compliance with industry, statutory or HSBEI guidelines, nor does it guarantee that fire related losses will not occur.

    Construction insurance solutions

    We have a comprehensive range of construction insurance products covering all aspects of projects across the UK and Ireland.